Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
|
|
|
|
Generator Set Specifications
- Maximum Rating
- 60 ekW
- Minimum Rating
- 60 ekW
- Emissions/Fuel Strategy
- U.S. EPA Cert., Tier 3
- Voltage
- 208 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1,800 rpm
- Duty Cycle
- Standby
Engine Specifications
- Engine Model
- C4.4, In-line 4, 4-cycle diesel
- Bore
- 4.1 in
- Stroke
- 5 in
- Displacement
- 269 in
- Compression Ratio
- 16.7:1
- Aspiration
- Turbocharged
- Fuel System
- Electronic (adjustable)
- Governor Type
- Mechanical, ADEM™A4
Generator Set Dimensions
- Length - Maximum
- 77.2 in
- Width - Maximum
- 43.3 in
- Height - Maximum
- 48 in
- Dry Weight - Genset (maximum)
- 2,054 lb
Standard Equipment:
-
- Certificates
-
- IBC seismic and wind Certifications
-
- Air Inlet System
-
- Air cleaner
- Cartridge type air filter
-
- Circuit Breakers
-
- Breakers (100% UL rated)
- 3-Pole 100% rated
- Second circuit breaker box
- Power terminal strip
-
- Charging System
-
- NFPA battery charger UL10A 120VAC
-
- Control Panel
-
- GCCP 1.2 Control panel
-
- Exhaust System
-
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
- Fuel System
-
- Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
-
- Control Panels
-
- WSS1 Low coolant level shut down
- FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected
- NFPA110 bundle includes:
- WCA1 Low coolant temperature alarm
- A Coolant heater, remote annunciator or 0.8 power factor test may be required depending on the application
- PBC10NU NFPA battery charger
- Oil temperature gauge and sender
- PAA1 Panel mounted audible alarm
- Ground fault relay
- Remote E-stop button
- Remote annunciator module
- Audible alarm
- Volt free contacts genset run and common alarm
- Discrete I/O module
- Overload shutdown via breaker
- Low coolant temperature alarm
- Protective devices:
- Fuel level reading
- Low coolant level shutdown
-
- Cooling System
-
- Coolant drain line with valve
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
- Radiator and cooling fan with guards
- Radiator stone guard
-
- Generator
-
- 12 Leads
-
- Governing System
-
- Mechanical and electrical governing system - model dependent
-
- Lube System
-
- Oil drain line with valve
- Lubricating oil
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
-
- Starting/charging System
-
- Batteries
- 24V battery with rack and cables
Optional Equipment:
-
- Certificates
-
- IBC seismic and wind Certifications
-
- Alternator System
-
- R Frame auxilliary winding
-
- Air Inlet System
-
- Cartridge type air filter
-
- Charging System
-
- NFPA battery charger UL10A 120VAC
-
- Circuit Breakers
-
- Breakers (100% UL rated)
- 3-Pole 100% rated
- Second circuit breaker box
- Power terminal strip
-
- Control Panels
-
- NFPA110 bundle includes: FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected - WSS1 Low coolant level shut down - WCA1 Low coolant temperature alarm - PAA1 Panel mounted audible alarm - PBC10NU NFPA battery charger - A Coolant heater ,remote annunciator or 0.8 power factor test may be required depending on the application
- Ground fault relay
- Remote E-stop button
- Volt free contacts genset run and common alarm
- Oil temperature gauge and sender
- Audible alarm
- Remote annunciator module
- Protective devices: Low coolant temperature alarm - Low coolant level shutdown - Fuel level reading - Overload shutdown via breaker
- Discrete I/O module
-
- Cooling System
-
- Radiator transition flange
-
- Enclosures
-
- Sound attenuated enclosure, Level 1
- External emergency stop
- Sound attenuated Level 2 Enclosure (White)
- Panel viewing window
-
- Exhaust System
-
- 10, 25 and 35 dBA silencer systems
- Overhead silencer mounting kit
-
- Fuel System
-
- Emergency vent pipe
- Tank riser
- 5 Gallon spill containment
- 209 and 394 gallon sub-base fuel tanks
- 5 Gallon fill containment
-
- Heating Elements
-
- Battery heater
- Jacket water heater
- Coolant heater
- Anti-condensation heater
- Wiring for canopy space heater
- Lube oil sump heater
-
- Generators
-
- Permanent magnet excitation (PMG) generator
- Cat Alternator
-
- Mounting System
-
- Seismic vibration isolators
-
- Tests
-
- 4 Hour factory test
- Generator test report
- PGS Test report @ 0.8 power factor
- PGS Test report @ 1.0 power factor
Specifications
Generator Set Specifications
- Maximum Rating
- 60 ekW
- Minimum Rating
- 60 ekW
- Emissions/Fuel Strategy
- U.S. EPA Cert., Tier 3
- Voltage
- 208 to 600 Volts
- Frequency
- 60 Hz
- Speed
- 1,800 rpm
- Duty Cycle
- Standby
Engine Specifications
- Engine Model
- C4.4, In-line 4, 4-cycle diesel
- Bore
- 4.1 in
- Stroke
- 5 in
- Displacement
- 269 in
- Compression Ratio
- 16.7:1
- Aspiration
- Turbocharged
- Fuel System
- Electronic (adjustable)
- Governor Type
- Mechanical, ADEM™A4
Generator Set Dimensions
- Length - Maximum
- 77.2 in
- Width - Maximum
- 43.3 in
- Height - Maximum
- 48 in
- Dry Weight - Genset (maximum)
- 2,054 lb
Standard/Optional Features
Standard Equipment:
-
- Certificates
-
- IBC seismic and wind Certifications
-
- Air Inlet System
-
- Air cleaner
- Cartridge type air filter
-
- Circuit Breakers
-
- Breakers (100% UL rated)
- 3-Pole 100% rated
- Second circuit breaker box
- Power terminal strip
-
- Charging System
-
- NFPA battery charger UL10A 120VAC
-
- Control Panel
-
- GCCP 1.2 Control panel
-
- Exhaust System
-
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
-
- Fuel System
-
- Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
-
- Control Panels
-
- WSS1 Low coolant level shut down
- FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected
- NFPA110 bundle includes:
- WCA1 Low coolant temperature alarm
- A Coolant heater, remote annunciator or 0.8 power factor test may be required depending on the application
- PBC10NU NFPA battery charger
- Oil temperature gauge and sender
- PAA1 Panel mounted audible alarm
- Ground fault relay
- Remote E-stop button
- Remote annunciator module
- Audible alarm
- Volt free contacts genset run and common alarm
- Discrete I/O module
- Overload shutdown via breaker
- Low coolant temperature alarm
- Protective devices:
- Fuel level reading
- Low coolant level shutdown
-
- Cooling System
-
- Coolant drain line with valve
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
- Radiator and cooling fan with guards
- Radiator stone guard
-
- Generator
-
- 12 Leads
-
- Governing System
-
- Mechanical and electrical governing system - model dependent
-
- Lube System
-
- Oil drain line with valve
- Lubricating oil
-
- General
-
- Engine and alternator pre-paint, Caterpillar yellow
-
- Starting/charging System
-
- Batteries
- 24V battery with rack and cables
Optional Equipment:
-
- Certificates
-
- IBC seismic and wind Certifications
-
- Alternator System
-
- R Frame auxilliary winding
-
- Air Inlet System
-
- Cartridge type air filter
-
- Charging System
-
- NFPA battery charger UL10A 120VAC
-
- Circuit Breakers
-
- Breakers (100% UL rated)
- 3-Pole 100% rated
- Second circuit breaker box
- Power terminal strip
-
- Control Panels
-
- NFPA110 bundle includes: FSS Low fuel level alarm & indication panel circuitry required when sub-base tank is selected - WSS1 Low coolant level shut down - WCA1 Low coolant temperature alarm - PAA1 Panel mounted audible alarm - PBC10NU NFPA battery charger - A Coolant heater ,remote annunciator or 0.8 power factor test may be required depending on the application
- Ground fault relay
- Remote E-stop button
- Volt free contacts genset run and common alarm
- Oil temperature gauge and sender
- Audible alarm
- Remote annunciator module
- Protective devices: Low coolant temperature alarm - Low coolant level shutdown - Fuel level reading - Overload shutdown via breaker
- Discrete I/O module
-
- Cooling System
-
- Radiator transition flange
-
- Enclosures
-
- Sound attenuated enclosure, Level 1
- External emergency stop
- Sound attenuated Level 2 Enclosure (White)
- Panel viewing window
-
- Exhaust System
-
- 10, 25 and 35 dBA silencer systems
- Overhead silencer mounting kit
-
- Fuel System
-
- Emergency vent pipe
- Tank riser
- 5 Gallon spill containment
- 209 and 394 gallon sub-base fuel tanks
- 5 Gallon fill containment
-
- Heating Elements
-
- Battery heater
- Jacket water heater
- Coolant heater
- Anti-condensation heater
- Wiring for canopy space heater
- Lube oil sump heater
-
- Generators
-
- Permanent magnet excitation (PMG) generator
- Cat Alternator
-
- Mounting System
-
- Seismic vibration isolators
-
- Tests
-
- 4 Hour factory test
- Generator test report
- PGS Test report @ 0.8 power factor
- PGS Test report @ 1.0 power factor