Cat Gas Generator Sets - G3520 with FAST RESPONSE For Sale 11219 7

Cat Gas Generator Sets - G3520 with FAST RESPONSE For Sale 11219

G3520 2000kW Gas Generator Set
11219 Cat Gas Generator Sets - G3520 with FAST RESPONSE For Sale 11219 8
CAT
Power Systems
Price: Request a Quote
Gas Standby Rating
2,000 ekW @ 0.8pf
Fuel Type
Natural Gas, Hydrogen Blend (up to 5%)
Emissions/Fuel Strategy
U.S. EPA Stationary Non-Emergency Certified
Frequency
60 Hz

Generator Set Specifications

Gas Standby Rating
2,000 ekW @ 0.8pf
Fuel Type
Natural Gas, Hydrogen Blend (up to 5%)
Emissions/Fuel Strategy
U.S. EPA Stationary Non-Emergency Certified
Frequency
60 Hz
RPM
1,800 rpm
Compression Ratio
11.5

Engine Specifications

Engine Model
G3,520
Displacement
5,956 in³
Aspiration
TA
Bore
6.7 in
Stroke
8.5 in

Generator Set Dimensions

Length
336 in
Width
94 in
Height
128 in
Weight
48,500 lb

Specifications

Generator Set Specifications

Gas Standby Rating
2,000 ekW @ 0.8pf
Fuel Type
Natural Gas, Hydrogen Blend (up to 5%)
Emissions/Fuel Strategy
U.S. EPA Stationary Non-Emergency Certified
Frequency
60 Hz
RPM
1,800 rpm
Compression Ratio
11.5

Engine Specifications

Engine Model
G3,520
Displacement
5,956 in³
Aspiration
TA
Bore
6.7 in
Stroke
8.5 in

Generator Set Dimensions

Length
336 in
Width
94 in
Height
128 in
Weight
48,500 lb

Standard/Optional Features

Standard Equipment:

  • Air Inlet
    • Two-element single-stage air cleaner with enclosure and service indicator
  • Control Panel
    • Cat ECS 100
  • Cooling
    • Jacket water and SCAC engine-driven pumps
    • Jacket water and SCAC thermostats
  • Exhaust
    • Dry exhaust manifolds, insulated and shielded
    • Cat-flanged face outlet on turbocharger
    • Individual exhaust port and turbocharger outlet wired to integrated temperature sensing module (ITSM) with GCEM providing alarms and shutdowns
  • Fuel System
    • Fuel system is sized for 31.5 to 47.2 MJ/NM3 dry pipeline natural gas with pressure of 10.2 to 34.5KPa to the engine fuel control valve
    • Engine-installed electronic control valve
    • Gas pressure regulator
    • Throttle plate, 24V DC actuator, controlled by GECM
    • 24V DC energized-to-run (ETR) gas shutoff valve
  • General
    • Parts book
    • Paint- Caterpillar Yellow with high gloss black rails and radiator
    • Operation and maintenance manuals
    • Crankshaft vibration damper and guard
    • RH Service
  • Generator
    • Permanent Magnet Excitiation
    • Integrated voltage regulator (IVR)
    • SR5
    • Winding temperature detectors
    • Anti-condensation space heater
    • NEMA Class H insulation
  • Starting/charging
    • 24V starting motors
    • Battery with cables and rack (shipped loose)
    • Jacket water heater
    • Electric Starter
  • Governing System
    • ADEM A4
  • Ignition System
    • Electronic Ignition System (controlled by ADEM A4)
    • Individual Cylinder Detonation Sensitive Timing (DST)

Optional Equipment:

  • Air Inlet
    • Air cleaner with precleaner
  • Control Panel
    • EMCP 4.4
    • Local alarm module
    • Engine failure relay
    • Remote annunciator
    • Remote PC monitoring
    • Local PC monitoring
  • Circuit Breakers
    • 1600A, 2000A 3 Pole, UL-100% Rated R-Frame Circuit Breakers
    • 100% rated, 3-pole (UL/CSA/IEC) 5th Digit Rating
    • S LSI, G LSIG, P LSIG-P, 4th Digit Type
    • Frame mounting
    • 3-pole (IEC 947-2 rated)
    • 2000A, 2500A, 3000A 3 Pole, UL-100% Rated Masterpact Circuit Breakers
  • Cooling
    • Package mounted radiator
    • Coolant level drain line with valves, fan with guard
  • Exhaust
    • 18, 25 dBA Attenuation
    • 305mm (12 in) spark arresting muffler
    • 305 mm (12in.) elbow
    • 305 mm (12 in.) flange
    • 305 mm (12 in.) muffler
  • Fuel System
    • 3, 0-100 kPag, 4-20mA gas train pressure sensors
  • General
    • Digital diagnostic tool
  • Generator
    • Bearing temperature detectors
    • Generator air filter
    • Cable access box
    • European bus bars
    • Low voltage extension box
  • Starting/charging
    • 20A, 24VDC battery charger
    • 45A, 24V charging alternator (requires engine driven pumps)
  • Grid Code Compliance
    • 60 Hz: USA